One morning the graphs of my heat pump shot up to 1200 °C. Flow and return, both of them. My LG Therma V reporting 1200 °C is not a heat pump running wild; it is an error value. But without countermeasures it ruins your graphs and your COP for months.

Where the 1200 °C comes from

When the Control Unit of the LG Therma V R290 has no contact with the outdoor unit, it returns fixed values via Modbus:

ValueWhat the LG reports
Error code237
Flow and return1200.0 °C (raw 12000)
Outdoor temperature25.5 °C

I also saw −64.9 and 300.0 °C on sensors that do not exist on this unit.

Why cleaning up afterwards does not work

My first reaction was to wipe the wrong values from the database with recorder.purge_entities. The graphs kept running up to 1200 °C. That service clears the normal history, but not the long-term statistics that the graphs draw on for longer periods.

The fix: never let the LG Therma V 1200 value in

The Home Assistant Modbus integration has the nan_value option: a raw value that means “not available”. If the sensor receives that value, it becomes unavailable instead of 1200. An example for the flow temperature:

modbus:
  - name: lg_therma_v
    type: serial
    port: !secret lg_heatpump_modbus_port
    baudrate: 9600
    bytesize: 8
    parity: N
    stopbits: 1
    sensors:
      - name: hp_outlet_temp
        slave: 33
        address: 3
        input_type: input
        scale: 0.1
        precision: 1
        unit_of_measurement: "°C"
        device_class: temperature
        nan_value: 12000

Check addresses and scale against the Modbus documentation for your model. In addition:

  • The heat pump graphs have a fixed y-axis, so an outlier that still gets through does not flatten the rest.
  • The COP calculation does not use unavailable values.

More status messages from the LG that you should not blindly believe: which status bits you should not trust. All incidents: Lessons from practice (in Dutch).


These values apply to one installation. Check them against your own documentation; leave work on 230/400 V to a qualified electrician.